1Are BBC Cellpack insulation tapes (e.g. No. 128) suitable for repairing cables and cores?
As long as only the cable sheath (outer plastic) is damaged, the insulating tape is suitable as temporary protection. Sealing against moisture is not guaranteed. However, if the basic insulation is also damaged, a simple insulating tape is no longer sufficient. In this case, the use of a gel, cast resin or shrink sleeve is recommended. Of course, the same applies to damage to the conductor
2Are the BBC Cellpack SHE house connection points suitable for feed-through in a floor slab, as a replacement for e.g. a multi-branch house connection point?
The SHE house entry is not suitable for implementation in floor slabs.
3The outer sheath of an E90 cable is damaged. Can a shrinkable sleeve be used for repairs?
Whether a shrink sleeve is possible for cable sheath repair is up to the damage assessment of the cable manufacturer. The shrink sleeve is only used for mechanical protection and prevents moisture from penetrating. The shrink sleeve does not meet any conducive properties for the operation of E90.
4Are there minimum distances that must be maintained for cast resin or gel systems?
In order to be able to establish a safe electrical connection, a minimum distance of 5mm is prescribed in the low voltage (up to 1kV) between the terminals/connectors/wires to the molded shell or the housing of the junction box. For non-insulated connectors, the 5mm also applies between the individual connectors.
Individual dimensions in the Cellpack assembly instructions may vary depending on the product.
5Is there a statement about the general UV resistance of self-welding tapes for above-ground installation?
The self-sealing tapes with UV stabilisation offered by BBC Cellpack are listed in the catalogue in the overview table.
UV-resistant is usually used colloquially to show that the properties of a material do not change or do not change significantly due to UV radiation.
UV-stabilized specifies relevant environmental conditions (e.g. irradiance, irradiation duration). UV irradiation can change the properties of the tapes within an acceptable range.
UV-resistant is generally used as a colloquial term to indicate that the properties of a material do not change at all or not significantly due to UV irradiation. UV-stabilised specifies relevant ambient conditions (e.g. (e.g. irradiance and irradiation duration). UV irradiation can alter the properties of the tapes within acceptable limits.
6Do BBC Cellpack's gel products have an effect on rubber cable sheaths (e.g.: H07RN-F) and can they be used?
The end products Gel from BBC Cellpack are made of cross-linked silicone. Once a silicone is cross-linked, there are no restrictions on compatibility.
7Are BBC Cellpack heat shrinkable cable joints, cast resin joints or gel joints approved for use in hazardous areas?
At the present time, there is no approval for use in hazardous areas.
8In what temperature range can the BBC Cellpack EASYCELL joints be mounted?
The BBC Cellpack EASYCELL joints can be mounted in a range of -10 °C to +60 °C. After installation, the joints can be operated in the temperature range from -20 °C to +90 °C.
After installation, the joints can be operated in a temperature range from -20°C to +90°C.
9Is it possible to connect or branch off several cables using an Easycell branch joint?
The joint shell and the associated branch block are designed to accommodate a continuous main cable and a branch cable.
10To which extent do cast resin joints protect against the penetration of gases?
The DIN EN 50393 test standard does not include testing of the entire system for the influence of gases. In addition, changes in properties depending on the substance and the concentration have not been tested.
Changes in the properties depending on the substance and concentration are also not tested.
11To which extent do cast resin joints protect against the penetration of water?
The casting resin systems protect against the ingress of water up to 1m water depth, provided that they are correctly installed and comply with the instructions in the installation instructions. The DIN EN 50393 test standard provides corresponding tests with a water depth of 1m
Test standard DIN EN 50393 contains corresponding tests at a water depth of 1m.
12Is SR installation of SMH possible under plaster?
The heat shrink sets offered by BBC Cellpack are suitable for installation under plaster. The use of individual hoses without hot melt glue is not recommended, as in this case there is no protection against the ingress of moisture and the insulating function of the hose over the remote cable cannot be fulfilled.
13Can BBC Cellpack cast resin also be used in connection with other housing shapes (e.g. branch box)?
In principle, this is not a problem as long as the housing is sealed during sealing, or the casting resin cannot escape after sealing until it has hardened
14Is it possible, to use clamps in spring clamp technology in combination with Cellpack sealing compounds (gel / cast resin)?
The applicability of WAGO's spring clamp technology has been tested and approved for applications using PUR gel as well as for Cellpack cast resin types EG and CG. Beyond these approvals, there is still no experience or test results as to how Cellpack's various other available sealing materials affect the plastic material of the terminals and whether the casting resins or gels have an effect on the long-term quality of the contact behaviour of the terminals. Confirmation of use for other types of casting resin is therefore not possible at present and can only be done after further tests.
15Can a hot-air blower also be used to shrink heat shrinkable components?
Heat-shrink components are components that shrink back to their original production state when heat is applied, such as: dividing caps, end caps, hoses or sleeves. A heat gun can be used for shrinking. However, the heat input is lower compared to a gas burner. This will extend the duration of the shrinking process. The settings and nozzle can be selected individually depending on the heat gun used. It is important to make sure that there are no burns on the surface of the heat shrink tube.
If it is a hose with hot melt adhesive (SRH...), the adhesive will slowly leak out at both ends. Important indications for correct shrinkage are uniform wall thicknesses and straight labeling.
16Can the Easycell® joint also be used as an end joint?
This use is generally possible. However, it has to be ensured that sufficient gel is displaced. This means that both gel surfaces must close around the cable end to ensure a seal against moisture.
17Can a polyurethane 2-component cast resin be used after the best-before date?
2 components cast resins usually have formulations with components of different properties. Use within the best-before date guarantees safe handling and ensures function in the approved application. If the best-before date is exceeded, the mixture can still work, but deviations in the properties are possible.
18Can an Easycell® joint also be installed at cold temperatures?
The Easycell® joints can be installed in a range from -10°C to +60°C. As with all other joints, care must also be taken that there is no moisture in the entire gel joint area, snow and ice included.
19Can a cast resin joint be encapsulated under tension?
The joint can be put into operation immediately after sealing, i.e. it can also be encapsulated under tension. The relevant "work under live regulations" must be observed.
20Can I make my own joint from various heat shrinkable tubes?
Our joints undergo complex test procedures such as the EN 50393 test standard. In this way, we guarantee that our joints also work permanently and are safe. In order not to have to take on this responsibility, we strongly advise against it.
21Can BBC Cellpack DR / DR-L crimp connectors, such as those included in the Easy-Fix repair kit, be used for solid conductors?
If there is a second pressing point in the component application of the DR-L connectors, it can be used on solid conductors. Since the DR connectors are shorter and only one pressing point is possible, the component application for solid conductors is not possible. The common crimping pliers can have 2 crimping points in the jaws, which means that with the DR-L the pliers are applied 2x for left and right, whereas with the DR the pliers with 1x pressing process crimp both sides. Again, the EASY-FIX system application on solid conductors is given.
22Can BBC Cellpack EASYCELL® be used in water?
All EASYCELL® joints are tested in accordance with test standard DIN EN 50393. This standard requires for the load to be changed with 0.1 bar water pressure. This means that the joint can be used in water depths of up to 1m. The instructions for installation must be observed.
23Can the SRMAHV shrinkable sleeves also be used to repair a cable jacket in low or medium voltage cables?
The decision as to whether a cable sheath can be repaired lies with the person responsible in the network. This depends on the damage and the properties that the cable sheath fulfils. In general, a cable may only be repaired with a sleeve if the damage only affects the outer sheath of the cable. If additional damage to the core insulation is detected, repair by means of a cuff is not permitted. The cable must then be repaired as a complete system, either with additional insulating and sealing components over the damaged wire(s) or, if necessary, by installing a connection sleeve over the damaged cable piece.If the decision is made to repair by means of a shrink sleeve, the sleeve must be selected on the basis of the values mentioned in the catalogue.
When choosing the right cuff, the operating voltage of the cable is not decisive. The function of sleeves is described below – restoration of the cable outer jacket in its three functions: insulation, protection against moisture and mechanical protection.
24Can three cable ends be interconnected?
Straight-through joints are designed for butt jointing two cables. Branch joints, on the other hand, are intended for a main conductor (which is not cut) and an outgoing cable. It is very difficult to join all three cable ends in one joint due to the lack of volume inside the shell and the need for special connectors. In addition, BBC Cellpack's standard joints were not designed for this application. We recommend using the following constellation to ensure a reliable and secure connection:
One exception to this rule are the two cast resin branch joints T1/EG/V/WAGO and Y1/EG/V/WAGO. They can be used to connect or branch three cable ends with up to 5x 0.5mm² - 5x 4mm² in one joint. The set contains 5 pieces of each WAGO COMPACT 221-413 series splicing connector.
25Can cast resin joints that were not completely cast during installation still be fully cast at a later point in time?
Such joints cannot be subsequently filled with cast resin, since proper casting cannot be guaranteed. (Various environmental conditions, such as temperature, humidity or dirt affect the result. These conditions have not been checked.)
26Are BBC Cellpack sets resistant to organic fertilisers?
Organic fertilisers are composed of different chemical substances, such as ammonia or nitrate in varying concentrations. As a result, it is not possible to carry out a meaningful test of the sets with regard to organic fertilisers.
27Are BBC Cellpack sealing compounds resistant to petrol?
BBC Cellpack's polyurethane-based sealing compounds are susceptible to petrol, which can affect their properties.
28Can the EASYCELL straight-through joints be combined with CU conductors and AL conductors?
Yes, EASYCELL 3V, 4V and 5V can be combined with CU conductors and AL conductors, since they have a tin-plated connection block with separator.
29Are gel joints suitable for multiple use (reusability)?
The gel joints from the EASYCELL®, EASY-PROTECT and EASY-PROTECT Inline product range are designed for single use only.
30Do BBC Cellpack tubes – type SR(H), SRAT and SRBB – contain chlorine and sulphur?
Cellpack hoses SR(H), SRAT, SRBB do not contain chlorine (nor any other halogenated materials), sulphur and no heavy metals or substances that are hazardous to health. A corresponding RohS and Reach conformity confirmation is available for the respective component.
31What should be considered with halogen-containing components and their use?
Important are the requirements of the customer/user for the end product and the requirement for its function in his operating environment,
In principle, halogen-free shrink components can also be used on halogen-containing cables (PVC) and halogen-containing shrink components (e.g. flame-retardant hoses) can also be used on halogen-free cables (PE, XLPE).
In general, halogen-free heat shrinkable components can also be used on cables that contain halogen (PVC) and heat shrinkable components that contain halogen (e.g. flame-retardant hoses) can generally also be used on halogen-free cables (PE, XLPE).
32What is the difference between hardening time and pot life?
The curing time describes the time required to achieve 100% curing of components A and B with the full mechanical properties. The pot life is a standardized term, which is also colloquially defined as a processing period. Depending on the different temperatures, fast or slow reactions are possible.
33What is the advantage of BBC Cellpack gels?
This new technology combines easy handling, label-free material and unlimited shelf life. The electrical properties after curing ensure a durable and reliable cable connection. To do this, we recommend keeping a minimum distance between the terminals/wires and the walls of the junction boxes.
34What is the advantage of BBC Cellpack cast resin joints?
Our casting resin systems have been tried and tested for decades. The electrical and mechanical properties after curing ensure a durable and reliable cable connection. Depending on the area of application, we offer a wide variety of casting resin variants.
35What is the advantage of BBC Cellpack heat shrinkable cable joints?
Our shrinkable products have been tried and tested for decades. The electrical and mechanical properties after cooling ensure a durable and reliable cable connection. A shrink product can also be ordered in advance, as they can be stored indefinitely.
36What is important to consider in connection with cast resin and rain / moisture?
Polyurethane (PUR) casting resins consist of two components, a resin and a hardener component. Components in the hardener component react more easily with water than with the PUR resin component as desired. In contact with moisture, the mixture will foam. In this case, the electrical and mechanical properties required are not met. For work under moisture, special casting resin systems such as UWR resin are available.
37What is the transport, storage, mounting and operation conditions for BBC Cellpack heat shrink joints and components for low voltage cables up to Umax = 1,2kV?
1. Instructions for transport and storage:
Storage
Temperature range 0...+40°C
Deviations from these conditions during storage can lead to restrictions in the function of individual components and, in individual cases, make assembly difficult or impossible.
2. Instructions for assembly:
Assembly instructions are supplied with each product (it is part of the kit). Temperature range for assembly/installation on these products: 0 to +40°C.
3. Operation:
Operating temperature range (always depending on the criteria of the cable):
SMH4 - Heat Shrink Joints for LV Cables - Operating Temperature Range of the Heat Shrink Tubing of the Kits -40°C to +120°C
SKH – Shrink End Caps -40°C to +100°C
SEH - Shrink Expansion Caps -40°C to +100°C
SRH3 - Heat Shrink Tubing with Thick Walls -40°C to +120°C
SRMAHV - Heat Shrink Tubing for Repair -40°C to +120°C
For more information on the individual product features, please refer to the product data sheet.
38What curing time does the EG casting resin require at what ambient temperature?
The curing time of the EC Casting Resin Casting Cloth depends on the ambient temperature, the component temperature and the amount of casting resin, more information on this can be found in the following diagram:

39What cast resins does Cellpack offer?
Cast resin have excellent electrical insulating properties. Different cast resins can be selected for different application areas:
EG: Universal casting resin for plastic, paper-insulated low-voltage cables, telecommunication cables and communication cables. In the case of medium-voltage cables, EG serves as protection against mechanical influences and moisture.
GG: Special casting resin for occupational safety due to reduced hazardous substance labelling. GG is suitable for plastic and paper-insulated low-voltage cables.
FG: The flexible casting resin is suitable for repairing damaged cable sheaths and connecting flexible cables.
UG: : Meets increased fire protection requirements and is used in mining.
UWR: : Characterized by its water resistance and allows potting under the influence of moisture.
WG: :The hardened molding material can be removed with light tools.
CG: Eco-friendly removable cold potting compound based on hydrocarbons. It is free of silicones, isocyanate and has no hazardous substance labeling.
40Which crimping pliers can be used for AVS and AVUS wire connectors?
The common crimping pliers on the market are to be used, please ask the manufacturer of your choice here.
41What temperatures must be observed when storing BBC Cellpack PUR cast resin products?
The recommended storage temperature of the PUR cast resin products offered by BBC Cellpack is between 15°C – 35°C.
42Which heat shrink tubing is UL (Underwriters Laboratories) approved?
The hoses type SR1F and SR1F3 are UL approved. Both hose types are listed in the UL directory under document number E172094
43How do I dispose of excess cast resin?
Unneeded casting resin hardens in the bag, after complete hardening it can simply be disposed of in the residual waste. The prerequisite for this is a complete mixture of components A and B.
44How does a heat shrink tube work?
A pipe is first extruded from polyolefin granules. Depending on the type of tube, the hot melt adhesive is also introduced (co-extruded) in this step. The tubes are then subjected to electron beam crosslinking. In the process, the molecular structure is changed, whereby the tubes receive a "memory". In a further step with heat supply, the tube is widened to the required diameter (expanded), then cooled down directly and finally cut.
When heated, the hose "remembers" its original state and shrinks back.
45What is the degree of protection (IPXX) of shrink sleeves and shrink tubing?
The LV shrink joints are subject to the requirements of the DIN EN 50393 standard. This standard describes precise test methods and test requirements for the fittings with a nominal voltage of 0.6/1.0 (1.2) kV. The standard properties and requirements for the heat shrink tubing are contained in the IEC 60684 standard (Part 1: Terms and General Requirements, Part 2: Test Methods, Part 3: Requirements for Individual Tubing Types).
The classification of degrees of protection (protection classes) is a component of DIN EN 60529 (VDE 0470). According to this standard, the extent of protection provided by an enclosure against access to hazardous parts, against the ingress of solid foreign bodies and/or against the ingress of water is demonstrated by standardised test methods. In both cases (LV shrink sleeves/hoses) there is no additional housing, which does not allow a test of the degree of protection.
46How to use the SVL shield connection cable?
In the installation instructions for the VASMI and SMHF telecommunication joints, this step is described as follows:
A) Prepare the cable cables according to the drawing:
Bild
The cables are prepared in the same way as for connecting joints, depending on the cable type.
B) Screen connection
Make the shield connection as with the connection sleeve. Install the shield connection branch terminal and cable (remove from MSFA and install according to the enclosed installation instructions).
The MSFA accessory set is only necessary for branch joints.
Bild
47What is the processing temperature and temperature resistance of BBC Cellpack POWER GEL?
The recommended processing temperature of BBC Cellpack POWER GEL is between +15 °C and +30 °C, while the temperature resistance is from -40 °C to +150 °C.
48How long does the cast resin have to be mixed?
During kneading, the resin and hardener mix and start an exothermic chemical reaction. An enclosed assembly instruction refers to a mixing time of the bag of 3 minutes. With a shorter mixing time, on the other hand, the components are not sufficiently mixed. Contrary to popular belief, the casting resin does not "dry", and if the reaction cannot occur, the mixture will not harden. In this case, the electrical and mechanical properties required are not met.
49How can pump lines be connected?
Pump lines differ from radial cables or cables due to their flat design, and fine-stranded conductors (conductor class 5) are also common. For these reasons, the following must be considered when selecting the joint and its installation:
• Maximum number of wires: 4 conductors per cable end.
• The arrangement of the connectors requires the use of spacer plates. These are already included in our cast resin joints M11, M12, M13S and M13.
• The joint must offer sufficient space for the insertion of the flat cable (max. cable Ø mm).
• Suitable crimp connectors and crimping tools must be used.
• To make it easier to seal the flat cable to the molded shell of the sleeve, it is recommended to use a sealing mastic such as our adhesive kit tape HKB (item no.: 127651).
50How do I mount a press cable lug?
There are different options:
There are different options here:
1) If it is a DIN connector, a suitable press device according to DIN is required. The crimp insert to be used is based on the outer diameter.
2) If it is a manufacturer-specific connector, the cross-section specification usually serves as the press insert.
In both cases, the pressure is from the center of the connector (according to the markings) towards the cable. The pressing makes the press connector a little longer. For this reason, a press allowance of 5mm (Cu) or 10mm (Al) is taken into account during cable preparation.
51How do I mount a screw connector (CSV, CSV-T, CSV-LHS)?
For these screw connectors with shear screws, all screws must be tightened one after the other during assembly. Then, with 2 screws per cable side, the screw to the cable is torn off first, followed by the screw to the connector center. In the case of a screw, it must be tightened evenly until it is torn off.
52How do I correctly shrink a spreader cap SEH...?
First, position the dividing cap on the cable splice. First, set the gas burner to a soft yellow flame. Now start heating the gusset (1) radially. Continue this movement while shrinking the shaft (2 -3) towards the cable jacket. Now switch back to the shaft and shrink the fingers (4) towards the vein regularly, also warming the inside of the splice.
After a short time, the glue slowly comes out at the end of the shaft and the dividing fingers. Important indications for correct shrinkage are uniform wall thicknesses and straight labeling.
53How do I shrink a heat shrink tube (SR...) correctly?
First, position the heat shrink tube. First, set the gas burner to a soft yellow flame. Now start heating radially from the center. Continue this movement while first shrinking one side completely. Now switch back to the center and repeat the process on the other side.
If it is a hose with hot melt adhesive (SRH...), the adhesive will slowly leak out at both ends. Important indications for correct shrinkage are uniform wall thicknesses and straight labeling. The following is an illustration from an assembly manual for a connection sleeve.
54How do I use the Cellpack cast resin?
Ideally, the bag has a temperature of approx. 20°C (STEP 1). Before mixing can begin, the bridge separating the resin and hardener must first be removed (STEP 2). Contact with the 2 components is not possible due to the closed mixing bag. During mixing, both components must be mixed into a homogeneous mixture if possible, following the time specified in the processing instructions (3 minutes) (STEP 3). Simply swirling or shaking the bag is not enough. To avoid casting resin losses as much as possible, it is recommended to brush the casting resin out of the corners and roll up the empty end (STEP 4, 5). Then a corner of the bag can be cut open to pour the casting resin into the sleeve (STEP 6). Below is an illustration of the assembly instructions with the individual steps.
BILD
55How is a heat shrink house entry SHE used?
How is a heat shrink house entry SHE used?
This is used for the simple introduction of cables and wires through walls into buildings.
To put it simply, this is a shrink tube that is positioned on a shaping metal spiral. Once installed, the cable is pushed through the house entry and sealed by simply heating the house entry ends. The installation is as follows:
First of all, a hole is drilled through the masonry, so that the drill bit with the right diameter is at hand, it is advisable to add the Cellpack data sheet. Cable centering can be used to align the house entry. If the distances are right, the preparation of the sealant can begin. This is mixed identically to the casting resin in a 2-chamber mixing bag, but has a significantly faster reaction time. A spatula is now used to create a homogeneous seal. Due to the short processing time, a separate bag can be used for the inside and outside.